Most split and packaged air conditioners sold today run on either R410A or R32. Distributors and importers usually need both: R410A to service the equipment already installed, and R32 for the newer units replacing it. This guide compares the two from a wholesale buyer's point of view.
The short comparison
| Property | R410A | R32 |
|---|---|---|
| Type | HFC blend, 50% R32 and 50% R125 | Single-component HFC (difluoromethane) |
| Global warming potential | 2,088 | 675 |
| Ozone depletion potential | 0 | 0 |
| Safety class | A1, non-flammable | A2L, mildly flammable |
| Transport class | 2.2 | 2.1 (UN 3252) |
Why the market is moving to R32
R32 has about one third of the global warming potential of R410A, and systems designed for it need a smaller refrigerant charge. As HFC phase-down schedules tighten under the Kigali Amendment and regional rules such as the EU F-gas Regulation, manufacturers have shifted new residential and light commercial units to R32.
Why R410A demand continues
An R410A system cannot simply be topped up with R32. The equipment, components and safety requirements are different, so every R410A unit in service will need R410A until it is replaced. For distributors, that means years of steady service demand.
What changes for handling and shipping
- Flammability: R32 is classed as flammable for transport, which affects freight booking, storage and the cylinders and valves used.
- Cylinders: both gases work at high pressure and need cylinders rated for it. R32 cylinders use fittings intended for flammable gas.
- Documents: safety data sheets and dangerous-goods declarations differ between the two, so order them per product.
Package sizes
R410A is commonly supplied in 11.3kg disposable cylinders, refillable cylinders, small canisters and ISO tanks. R32 is supplied in refillable cylinders, small high-pressure canisters and bulk tanks. Current options are listed in our R410A gas and R32 gas categories.
How to plan your stock
Look at what is installed in your market, not only at what is being sold new. Where most installed units are less than ten years old and run on R410A, service demand for it will stay strong. Where new installations are mostly R32, build that range early, and make sure your storage and transport arrangements are approved for flammable gas.
Request a quote
Refrigerant Gas International supplies importers, distributors and service companies worldwide. To get a price, open any product in our product range, click Request a Quote and tell us the gas, package size, quantity and destination port. You can also reach our sales team through the contact page by email, phone or WhatsApp.
Frequently asked questions
Can R32 be used in an R410A air conditioner?
No. Use only the refrigerant the equipment was designed and labelled for.
Can you ship both gases in one container?
Mixed loads are often possible, but flammable and non-flammable gases follow different dangerous-goods rules. Tell us the mix you want and the destination, and we will confirm what the shipping line accepts.
Do you supply worldwide?
Yes, we quote to ports worldwide, subject to each country's import rules for HFCs.